Opis
Model | SUN-29.9K-SG01HP3-EU-BM3 | SUN-30K-SG01HP3-EU-BM3 | SUN-35K-SG01HP3-EU-BM3 | SUN-40K-SG01HP3-EU-BM4 |
SUN-50K-SG01HP3-EU-BM4 |
Battery Input Data | |||||
Battery Type | Lithium-ion | ||||
Battery Voltage Range (V) | 160~800 | ||||
Max. Charging Current (A) | 50+50 | ||||
Max. Discharging Current (A) | 50+50 | ||||
Number of Battery input | 2 | ||||
Charging Strategy for Li-Ion Battery | Self-adaption to BMS |
PV String Input Data | ||||||
Max. DC Input Power (W) | 38870 | 39000 | 45500 | 52000 | 65000 | |
Max. DC Input Voltage (V) | 1000 | |||||
Start-up Voltage (V) | 180 | |||||
MPPT Range (V) | 150-850 | |||||
Full Load DC Voltage Range (V) |
360-850
|
360-850
|
360-850
|
360-850
|
450-850
|
|
Rated DC Input Voltage (V)
|
600
|
|||||
PV Input Current (A) | 36+36+36 | 36+36+36 | 36+36+36 | 36+36+36+36 | ||
Max. PV ISC (A) | 55+55+55 | 55+55+55 | 55+55+55 | 55+55+55+55 | ||
No. of MPP Trackers | 3 | 4 | ||||
No. of Strings per MPP Tracker | 2+2+2 | 2+2+2+2 |
AC Output Data | |||||
Rated AC Output and UPS Power (W) | 29900 | 30000 | 35000 | 40000 | 50000 |
Max. AC Output Power (W) | 29900 | 33000 | 38500 | 44000 | 55000 |
AC Output Rated Current (A)
|
45.4/43.4 | 45.5/43.5 | 53.1/50.8 | 60.7/58 | 75.8/72.5 |
Max. AC Output Rated Current (A)
|
45.4/43.4 | 50/47.8 | 58.4/55.8 | 66.7/63.8 | 83.4/79.7 |
Max. AC Current (A) | 60 | 60 | 60 | 70 | 83.3 |
Max. Continuous AC Passthrough (A) | 200 | ||||
Peak Power (off grid) | 1.5 times of rated power, 10 S | ||||
Generator Input/Smart Load /AC Couple Current (A)
|
45.4/200/45.4 | 45.5/200/45.5 | 53.1/200/53.1 | 60.7/200/60.7 | 75.8/200/75.8 |
Power Factor Adjustment Range
|
0.8 leading to 0.8 lagging
|
||||
Output Frequency and Voltage | 50/60Hz;3L/N/PE 220/380Vac,230/400Vac | ||||
Grid Type | Three Phase | ||||
Total Harmonic Distortion (THD)
|
<3% (of nominal power)
|
||||
DC Current Injection | <0.5% ln |
Efficiency | |
Max. Efficiency | 97.60% |
Euro Efficiency | 97.00% |
MPPT Efficiency | 99.90% |
Protection | |
Integrated
|
Anti-islanding Protection, PV String Input Reverse Polarity Protection,
Insulation Resistor Detection, Residual Current Monitoring Unit, Output Over Current Protection,
Output Shorted Protection, Surge Protection
|
Over Voltage Category | DC Type II / AC Type ? |
Certifications and Standards | |
Grid Regulation | VDE4105, IEC61727/62116, VDE0126, AS4777.2, CEI 0 21, EN50549-1, G98, G99, C10-11, UNE217002, NBR16149/NBR16150 |
Safety EMC / Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |
General Data | |
Operating Temperature Range (?) | -40~60?, >45? Derating |
Cooling | Smart cooling |
Noise (dB) | ?65 dB |
Communication with BMS | RS485; CAN |
Weight (kg) | 80 |
Cabinet Size (WxHxD mm)
|
527×894×294 (Excluding Connectors and Brackets)
|
Protection Degree | IP65 |
Installation Style | Wall-mounted |